Earth Tester
2 mA measuring current
Test without tripping Earth Leakage Current
Type Tested as per BIS9223 : 79
- Data hold.
- IEC 1010 CAT.
- Battery operated.
- Capable of measuring earth voltage.
Ordering Code : 1520(Digital),1820(Digital) & 1505(Analog)
Request a Quote
click on image to enlarge
TECHNICAL SPECIFICATIONS
Measurement Ranges
Ordering Code: 1820ER
| Earth Resistance (in Ohms) | 0-20,0-200,0-2000 |
| Earth Voltage | 0-200V AC(50/60)Hz |
| ACCURACY | |
| Earth Voltage | +/_ (2% rdg + 2dgt) |
| Earth Resistance | +/_ (1% rdg + 2dgt) |
| Resolution | 0.01 ohms (20 ohms) Scale |
Ordering Code: 1520ER
| Earth Resistance (in Ohms) | 0-20,0-200,0-2000 |
| Earth Voltage | 0-200V AC(40-500)Hz |
| ACCURACY | |
| Earth Voltage | +/_ (1% rdg + 2dgt) |
| Earth Resistance | +/_ (2% rdg + 2dgt) |
| Resolution | 0.01 ohms (20 ohms) Scale |
Ordering Code: ST-1505
| Earth Resistance (in Ohms) | 0-10,0-100,0-1000 |
| Earth Voltage | 0-30V AC(40-500)Hz |
| ACCURACY | |
| Earth Voltage | +/_ (3% rdg + 2dgt) |
| Earth Resistance | +/_ (3% rdg + 2dgt) |
| Resolution | Analog Scale |